Overview of Velbus actions

image/svg+xml

To search through this document, press CTRL+F

List

  1. 01.
    General
    1. 0101.
      On
    2. 0102.
      Off
    3. 0103.
      Toggle
    4. 0104.
      Momentary (follow)
    5. 0105.
      Execute action set by hardware
    6. 0106.
      Up
    7. 0107.
      Immediately up
    8. 0108.
      Immediately up when initiator opens
    9. 0109.
      Immediately up
    10. 0110.
      Down
    11. 0111.
      Immediately down
    12. 0112.
      Immediately down when initiator opens
    13. 0113.
      Immediately down
    14. 0114.
      Up/down
    15. 0115.
      Go to position
    16. 0116.
      Go to position when initiator opens
    17. 0117.
      Comfort/III mode
    18. 0118.
      Day/II mode
    19. 0119.
      Night/I mode
    20. 0120.
      Safe/standby mode
    21. 0121.
      Heating mode
    22. 0122.
      Cooling mode
    23. 0123.
      Forced Safe mode
    24. 0124.
      Forced Safe mode while initiator is closed
    25. 0125.
      Forced Safe mode while initiator is open
    26. 0126.
      Cancel forced Safe mode
    27. 0127.
      Toggle forced Safe mode
    28. 0128.
      Lock local control
    29. 0129.
      Unlock local control
    30. 0130.
      Disable while initiator is closed
    31. 0131.
      Disable while initiator is open
    32. 0132.
      Force screensaver to off
    33. 0133.
      Cancel force screensaver to off
    34. 0134.
      Reset absence timer while initiator is closed
    35. 0135.
      Monitor status of initiator
    36. 0136.
      Comfort/III mode (continuous at long press, temporarily at short press)
    37. 0137.
      Day/II mode (continuous at long press, temporarily at short press)
    38. 0138.
      Night/I mode (continuous at long press, temporarily at short press)
    39. 0139.
      Safe/standby mode (continuous at long press, temporarily at short press)
    40. 0140.
      Set to mode 1
    41. 0141.
      Set to mode 2
    42. 0142.
      Set to mode 3
    43. 0143.
      Set to mode 4
  2. 02.
    Dimming
    1. 0201.
      Dim up/down
    2. 0202.
      Dim at long press, toggle at short press
    3. 0203.
      Dim at long press, memory or off at short press
    4. 0204.
      Dim up
    5. 0205.
      Dim up at long press, on at short press
    6. 0206.
      Dim up at long press, memory at short press
    7. 0207.
      Dim down
    8. 0208.
      Dim down at long press, off at short press
    9. 0209.
      Dim to set percent
    10. 0210.
      Dim to set percent over time
    11. 0211.
      Turn on gradually
    12. 0212.
      Turn off gradually
    13. 0213.
      Slave (following initiator)
    14. 0214.
      Atmospheric dimvalue
    15. 0215.
      Multi step dimmer
  3. 03.
    Dim slowly on / dim slowly off
    1. 0301.
      Slow on
    2. 0302.
      Slow on when initiator closes, slow off when initiator opens
    3. 0303.
      Slow off
    4. 0304.
      Slow on/off
  4. 04.
    Timer
    1. 0401.
      Start timer 1
    2. 0402.
      Toggle timer 1
    3. 0403.
      Start timer 2
    4. 0404.
      Toggle timer 2
    5. 0405.
      Start/stop timer
    6. 0406.
      Trigger-on-release timer
    7. 0407.
      Non-restartable timer
    8. 0408.
      Start/stop timer
    9. 0409.
      Start/stop timer with slow on/off
    10. 0410.
      Restartable timer
    11. 0411.
      Restartable timer with slow on/off
    12. 0412.
      Restartable timer
    13. 0413.
      Non-restartable timer
    14. 0414.
      Non-restartable timer with slow on/off
    15. 0415.
      Start/stop interval timer
    16. 0416.
      Restartable interval timer
    17. 0417.
      Non-restartable interval timer
  5. 05.
    Delays
    1. 0501.
      Start/stop delayed on
    2. 0502.
      Restartable delayed on
    3. 0503.
      Non-restartable delayed on
    4. 0504.
      On when initiator closes, delayed off when initiator opens
    5. 0505.
      Delayed off only when subject is on
  6. 06.
    Lock / unlock
    1. 0601.
      Lock channel
    2. 0602.
      Lock channel while initiator is closed
    3. 0603.
      Lock channel while initiator is open
    4. 0604.
      Unlock channel
    5. 0605.
      Lock/unlock channel
  7. 07.
    Inhibit
    1. 0701.
      Inhibit
    2. 0702.
      Inhibit while initiator is closed
    3. 0703.
      Inhibit while initiator is open
    4. 0704.
      Cancel inhibit
    5. 0705.
      Toggle inhibit
    6. 0706.
      Inhibit preset up
    7. 0707.
      Inhibit but preset up while initiator is closed
    8. 0708.
      Inhibit but preset up while initiator is open
    9. 0709.
      Cancel inhibit but preset up
    10. 0710.
      Toggle inhibit but preset up
    11. 0711.
      Inhibit preset down
    12. 0712.
      Inhibit but preset down while initiator is closed
    13. 0713.
      Inhibit but preset down while initiator is open
    14. 0714.
      Cancel inhibit but preset down
    15. 0715.
      Toggle inhibit but preset down
  8. 08.
    Forced
    1. 0801.
      Forced on
    2. 0802.
      Forced on while initiator is closed
    3. 0803.
      Forced on while initiator is open
    4. 0804.
      Cancel forced on
    5. 0805.
      Toggle forced on
    6. 0806.
      Forced off
    7. 0807.
      Forced off while initiator is closed
    8. 0808.
      Forced off while initiator is open
    9. 0809.
      Cancel forced off
    10. 0810.
      Toggle forced off
    11. 0811.
      Forced up
    12. 0812.
      Forced up while initiator is closed
    13. 0813.
      Forced up while initiator is open
    14. 0814.
      Cancel forced up
    15. 0815.
      Toggle forced up
    16. 0816.
      Forced down
    17. 0817.
      Forced down while initiator is closed
    18. 0818.
      Forced down while initiator is open
    19. 0819.
      Cancel forced down
    20. 0820.
      Toggle forced down
    21. 0821.
      Force to current position
    22. 0822.
      Force to current position while initiator is closed
    23. 0823.
      Force to current position while initiator is open
    24. 0824.
      Cancel force to current position
    25. 0825.
      Force/cancel force to current position
  9. 09.
    Programs
    1. 0901.
      Enable program steps for this channel
    2. 0902.
      Disable program steps for this channel
    3. 0903.
      Disable program steps for this channel while initiator is closed
    4. 0904.
      Disable program steps for this channel while initiator is open
    5. 0905.
      Toggle program steps for this channel
    6. 0906.
      Select no program
    7. 0907.
      Select program 1
    8. 0908.
      Select program 2
    9. 0909.
      Select program 3
    10. 0910.
      Toggle program 1
    11. 0911.
      Toggle program 2
    12. 0912.
      Toggle program 3
    13. 0913.
      Enable alarm/sunrise/sunset
    14. 0914.
      Enable alarm/sunrise/sunset while initiator is closed
    15. 0915.
      Enable alarm/sunrise/sunset while initiator is open
    16. 0916.
      Disable alarm/sunrise/sunset
    17. 0917.
      Disable alarm/sunrise/sunset while initiator is closed
    18. 0918.
      Disable alarm/sunrise/sunset while initiator is open
    19. 0919.
      Toggle alarm/sunrise/sunset
  10. 10.
    Clock alarms
    1. 1001.
      Enable Clock Alarm 1 related program steps
    2. 1002.
      Enable Clock Alarm 1 related program steps while initiator is closed
    3. 1003.
      Enable Clock Alarm 1 related program steps while initiator is open
    4. 1004.
      Disable Clock Alarm 1 related program steps
    5. 1005.
      Disable Clock Alarm 1 related program steps while initiator is closed
    6. 1006.
      Disable Clock Alarm 1 related program steps while initiator is open
    7. 1007.
      Toggle Clock Alarm 1 related program steps
    8. 1008.
      Enable Clock Alarm 2 related program steps
    9. 1009.
      Enable Clock Alarm 2 related program steps while initiator is closed
    10. 1010.
      Enable Clock Alarm 2 related program steps while initiator is open
    11. 1011.
      Disable Clock Alarm 2 related program steps
    12. 1012.
      Disable Clock Alarm 2 related program steps while initiator is closed
    13. 1013.
      Disable Clock Alarm 2 related program steps while initiator is open
    14. 1014.
      Toggle Clock Alarm 2 related program steps
    15. 1015.
      Enable Clock Alarm 1 related program steps
    16. 1016.
      Enable Clock Alarm 1 related program steps while initiator is closed
    17. 1017.
      Enable Clock Alarm 1 related program steps while initiator is open
    18. 1018.
      Disable Clock Alarm 1 related program steps
    19. 1019.
      Disable Clock Alarm 1 related program steps while initiator is closed
    20. 1020.
      Disable Clock Alarm 1 related program steps while initiator is open
    21. 1021.
      Toggle Clock Alarm 1 related program steps
    22. 1022.
      Enable Clock Alarm 2 related program steps
    23. 1023.
      Enable Clock Alarm 2 related program steps while initiator is closed
    24. 1024.
      Enable Clock Alarm 2 related program steps while initiator is open
    25. 1025.
      Disable Clock Alarm 2 related program steps
    26. 1026.
      Disable Clock Alarm 2 related program steps while initiator is closed
    27. 1027.
      Disable Clock Alarm 2 related program steps while initiator is open
    28. 1028.
      Toggle Clock Alarm 2 related program steps
  11. 11.
    Sunrise / Sunset
    1. 1101.
      Enable Sunrise related program steps
    2. 1102.
      Enable Sunrise related program steps while initiator is closed
    3. 1103.
      Enable Sunrise related program steps while initiator is open
    4. 1104.
      Disable Sunrise related program steps
    5. 1105.
      Disable Sunrise related program steps while initiator is closed
    6. 1106.
      Disable Sunrise related program steps while initiator is open
    7. 1107.
      Toggle Sunrise related program steps
    8. 1108.
      Enable Sunset related program steps
    9. 1109.
      Enable Sunset related program steps while initiator is closed
    10. 1110.
      Enable Sunset related program steps while initiator is open
    11. 1111.
      Disable Sunset related program steps
    12. 1112.
      Disable Sunset related program steps while initiator is closed
    13. 1113.
      Disable Sunset related program steps while initiator is open
    14. 1114.
      Toggle Sunset related program steps
    15. 1115.
      Enable sunrise related program steps
    16. 1116.
      Enable sunrise related program steps while initiator is closed
    17. 1117.
      Enable sunrise related program steps while initiator is open
    18. 1118.
      Disable sunrise related program steps
    19. 1119.
      Disable sunrise related program steps while initiator is closed
    20. 1120.
      Disable sunrise related program steps while initiator is open
    21. 1121.
      Toggle sunrise related program steps
    22. 1122.
      Enable sunset related program steps
    23. 1123.
      Enable sunset related program steps while initiator is closed
    24. 1124.
      Enable sunset related program steps while initiator is open
    25. 1125.
      Disable sunset related program steps
    26. 1126.
      Disable sunset related program steps while initiator is closed
    27. 1127.
      Disable sunset related program steps while initiator is open
    28. 1128.
      Toggle sunset related program steps
  12. 12.
    Disable timer
    1. 1201.
      On with timers disabled
    2. 1202.
      On with timers disabled at short press
    3. 1203.
      On with timers disabled at long press
    4. 1204.
      Off with timers disabled
    5. 1205.
      Off with timers disabled at short press
    6. 1206.
      Off with timers disabled at long press
    7. 1207.
      On with timers disabled/off
    8. 1208.
      On with timers disabled/off at short press
    9. 1209.
      On with timers disabled/off at long press
  13. 13.
    Mode selection
    1. 1301.
      Deselect mode
    2. 1302.
      Deselect mode when initiator opens
    3. 1303.
      Select mode 1
    4. 1304.
      Select mode 1 when initiator opens
    5. 1305.
      Toggle mode 1
    6. 1306.
      Select mode 2
    7. 1307.
      Select mode 2 when initiator opens
    8. 1308.
      Toggle mode 2
    9. 1309.
      Select mode 3
    10. 1310.
      Select mode 3 when initiator opens
    11. 1311.
      Toggle mode 3
  14. 14.
    Actions in mode 1
    1. 1401.
      Up, only in mode 1
    2. 1402.
      Immediately up, only in mode 1
    3. 1403.
      Immediately up when initiator opens, only in mode 1
    4. 1404.
      Down, only in mode 1
    5. 1405.
      Immediately down, only in mode 1
    6. 1406.
      Immediately down when initiator opens, only in mode 1
    7. 1407.
      Up/down, only in mode 1
    8. 1408.
      Go to position, only in mode 1
    9. 1409.
      Go to position when initiator opens, only in mode 1
  15. 15.
    Actions in mode 2
    1. 1501.
      Up, only in mode 2
    2. 1502.
      Immediately up, only in mode 2
    3. 1503.
      Immediately up when initiator opens, only in mode 2
    4. 1504.
      Down, only in mode 2
    5. 1505.
      Immediately down, only in mode 2
    6. 1506.
      Immediately down when initiator opens, only in mode 2
    7. 1507.
      Up/down, only in mode 2
    8. 1508.
      Go to position, only in mode 2
    9. 1509.
      Go to position when initiator opens, only in mode 2
  16. 16.
    Actions in mode 3
    1. 1601.
      Up, only in mode 3
    2. 1602.
      Immediately up, only in mode 3
    3. 1603.
      Immediately up when initiator opens, only in mode 3
    4. 1604.
      Down, only in mode 3
    5. 1605.
      Immediately down, only in mode 3
    6. 1606.
      Immediately down when initiator opens, only in mode 3
    7. 1607.
      Up/down, only in mode 3
    8. 1608.
      Go to position, only in mode 3
    9. 1609.
      Go to position when initiator opens, only in mode 3

01 General

0101. On

Description:

When the initiator closes or is pressed, the subject closes (on).

Diagrams:


Parameters:

None

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running

Examples:

On button

This action applies to:

0102. Off

Description:

When the initiator closes or is pressed, the subject opens (off).

Diagrams:

Parameters:

None

Feedback behaviour:

LED always off

Examples:

Off button

This action applies to:

0103. Toggle

Description:

Each time the initiator closes or is pressed, the subject toggles (if it was on, it is switched off; if it was off, it is switched on).

Diagrams:

Parameters:

None

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running

Examples:

On / off button

This action applies to:

0104. Momentary (follow)

Description:

As long as the initiator is open (off, released), the subject is open (off). As long as the initiator is closed (on, pressed), the subject is closed (on).

When several initiators are linked to the same subject using 0104. Momentary (follow) actions, they function as a logical OR: as long as one or more of the initiators is closed (pressed, on), the subject will be closed (on). Only when all initiators are open (off, released), the subject will be open (off).

Caution: this logical OR function will be cancelled if another action (eg. 0102. Off) intervenes.

Diagrams:



Parameters:

None

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running

Examples:

  1. Door bell (initiator = push button, subject = bell relay)
  2. As long as the lights in the toilet are on, a ventilator works (initiator = light relay, subject = ventilator relay)
  3. Automatically switch off the power supply of a dimmable fixture when the light is off (initiator = dimming channel, subject = relay controlling the power supply).

This action applies to:

0105. Execute action set by hardware

Description:

Execute the action defined by the rotary switches on the module.

Parameters:

None

This action applies to:

0106. Up

Description:

The initiator is a push button

  • short press: the blind goes up, either completely or until a down action is initiated.
  • long press: the blind goes up as long as the button is pressed. The motor stops when the button is released.
If the blind channel is in slat mode (cfr. blind configuration in Velbuslink), the functions for long and short press are inversed (firmware 1809 or higher).

If the blind was going down, a short or long press will stop the motor.

The initiator is a relay or sensor

The blind goes up when the initiator closes. If the blind was going down, it will stop. If the initiator is not a push button, in most cases the action 0109. Immediately up is more suitable.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes up, and is constantly lit when completely up

This action applies to:

0107. Immediately up

Description:

When the initiator closes or is pressed, the blind goes completely up. When a down action is started during the rolling up, the blind will stop.

Parameters:

None

This action applies to:

0108. Immediately up when initiator opens

Description:

When the initiator opens or is released, the blind goes up completely. When a down action is started during the rolling up, the blind will stop.

The motor only starts after the on delay.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes up, and is constantly lit when completely up

This action applies to:

0109. Immediately up

Description:

When the initiator closes or is pressed, the blind goes completely up. When a down action is started during the rolling up, the blind will stop.

The motor only starts after the on delay.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes up, and is constantly lit when completely up

This action applies to:

0110. Down

Description:

The initiator is a push button

  • short press: the blind goes down, either completely or until an up action is initiated.
  • long press: the blind goes down as long as the button is pressed. The motor stops when the button is released.

If the blind was going up, a short or long press will stop the motor.

The initiator is a relay or sensor

The blind goes down when the initiator closes. If the blind was going up, it will stop. If the initiator is not a push button, in most cases the action 0113. Immediately down is more suitable.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes down, and is constantly lit when completely down

This action applies to:

0111. Immediately down

Description:

When the initiator closes or is pressed, the blind goes completely down. When an up action is started during the rolling down, the blind will stop.

Parameters:

None

This action applies to:

0112. Immediately down when initiator opens

Description:

When the initiator opens or is released, the blind goes completely down. When an up action is started during the rolling down, the blind will stop.

The motor only starts after the on delay.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes down, and is constantly lit when completely down

This action applies to:

0113. Immediately down

Description:

When the initiator closes or is pressed, the blind goes completely down. When an up action is started during the rolling down, the blind will stop.

The motor only starts after the on delay .

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes down, and is constantly lit when completely down

This action applies to:

0114. Up/down

Description:

Single button control for up and down. The direction of the movement changes after each stop.

A short press will roll the blind completely up or down. A long press will roll it up or down as long as the button remains pressed.

If the blind was already moving, a short or long press will stop it.

Parameters:

None

Feedback behaviour:

LED blinks while the blind moves, is off when the blind is completely up and is constantly lit when completely down

This action applies to:

0115. Go to position

Description:

When the initiator closes or is pressed (and after expiration of the on delay), the blind will move to the configured position (adjustable between 0% and 100%).

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Position
    • 0% (compl. up) to 100% (compl. down)
    • Default value: 0% (compl. up)

Feedback behaviour:

LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position

This action applies to:

0116. Go to position when initiator opens

Description:

When the initiator opens or is released (and after expiration of the on delay), the blind will move to the configured position (adjustable between 0% and 100%).

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Position
    • 0% (compl. up) to 100% (compl. down)
    • Default value: 0% (compl. up)

Feedback behaviour:

LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position

This action applies to:

0117. Comfort/III mode

Description:

Switch the thermostat to comfort mode (when heating) or position III (when cooling).

The duration option Default sleep time refers to the sleep time configured in the module configuration settings.

Parameters:

  • Duration at short press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: Until next program step
  • Duration at long press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: No Action

Feedback behaviour:

LED on when thermostat is in corresponding mode (slow blinking if timer is running)

This action applies to:

0118. Day/II mode

Description:

Switch the thermostat to day mode (when heating) or position II (when cooling).

The duration option Default sleep time refers to the sleep time configured in the module configuration settings.

Parameters:

  • Duration at short press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: Until next program step
  • Duration at long press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: No Action

Feedback behaviour:

LED on when thermostat is in corresponding mode (slow blinking if timer is running)

This action applies to:

0119. Night/I mode

Description:

Switch the thermostat to night mode (when heating) or position I (when cooling).

The duration option Default sleep time refers to the sleep time configured in the module configuration settings.

Parameters:

  • Duration at short press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: Until next program step
  • Duration at long press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: No Action

Feedback behaviour:

LED on when thermostat is in corresponding mode (slow blinking if timer is running)

This action applies to:

0120. Safe/standby mode

Description:

Switch the thermostat to safe mode (when heating) or standby position (when cooling).

The duration option Default sleep time refers to the sleep time configured in the module configuration settings.

Parameters:

  • Duration at short press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: Until next program step
  • Duration at long press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: No Action

Feedback behaviour:

LED on when thermostat is in corresponding mode (slow blinking if timer is running)

This action applies to:

0121. Heating mode

Description:

Switch the thermostat to heating mode.

Parameters:

None

Feedback behaviour:

LED on when thermostat is in corresponding mode

This action applies to:

0122. Cooling mode

Description:

Switch the thermostat to cooling mode.

Parameters:

None

Feedback behaviour:

LED on when thermostat is in corresponding mode

This action applies to:

0123. Forced Safe mode

Description:

Switch the thermostat to forced safe mode (when heating) or forced standby mode (when cooling). The thermostat will remain in forced safe (or standby) mode until cancelled by action 0126. Cancel forced Safe mode or 0127. Toggle forced Safe mode.

When forced mode is cancelled, the thermostat returns to the last mode before forcing.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on when thermostat is in forced safe mode

This action applies to:

0124. Forced Safe mode while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the thermostat is set to forced safe mode (when heating) or forced standby mode (when cooling). The thermostat will remain in forced safe (or standby) mode until the initiator opens (switches off) again.

Parameters:

None

Feedback behaviour:

LED on when thermostat is in forced safe mode

This action applies to:

0125. Forced Safe mode while initiator is open

Description:

As long as the initiator is open (off, released), the thermostat is set to forced safe mode (when heating) or forced standby mode (when cooling). The thermostat will remain in forced safe (or standby) mode until the initiator closes (switches on) again.

Parameters:

None

Feedback behaviour:

LED on when thermostat is in forced safe mode

This action applies to:

0126. Cancel forced Safe mode

Description:

Cancel 0123. Forced Safe mode. When forced mode is cancelled, the thermostat returns to the last mode before forcing.

Parameters:

None

Feedback behaviour:

LED on when forced safe mode is cancelled

This action applies to:

0127. Toggle forced Safe mode

Description:

This action combines 0123. Forced Safe mode and 0126. Cancel forced Safe mode. If the thermostat was in forced mode when the initiator closes, action 0126. Cancel forced Safe mode will be executed. If the thermostat was not in forced mode when the initiator closes, action 0123. Forced Safe mode will be executed.

The duration parameter only applies to the forcing, not to the cancelling.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on when thermostat is in forced safe mode (slow blinking if timer is running)

This action applies to:

0128. Lock local control

Description:

Locks the local control button on the module, so users can no longer control the thermostat by pressing the button on the module. See also 0129. Unlock local control.

Parameters:

None

Feedback behaviour:

LED on when local control is locked

This action applies to:

0129. Unlock local control

Description:

Unlocks the local control button on the module, so users can control the thermostat again by pressing the button on the module. See also 0128. Lock local control.

Parameters:

None

Feedback behaviour:

LED on when local control is unlocked

This action applies to:

0130. Disable while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the thermostat is inhibited and set to safe mode (when heating) or standby position (when cooling).

Parameters:

None

Feedback behaviour:

LED on when thermostat is inhibited and in safe mode

Examples:

A (normally open) window contact turns off the heating when the window is open.

This action applies to:

0131. Disable while initiator is open

Description:

As long as the initiator is open (off, released), the thermostat is inhibited and set to safe mode (when heating) or standby position (when cooling).

Parameters:

None

Feedback behaviour:

LED on when thermostat is inhibited and in safe mode

Examples:

A (normally closed) window contact turns off the heating when the window is open.

This action applies to:

0132. Force screensaver to off

Description:

Override screensaver settings of the subject module and force its screensaver to off (instead of dimmed).

Parameters:

None

Feedback behaviour:

LED on when screensaver mode is forced to off

Examples:

Eg. for a bedroom, to avoid unwanted illumination by the oled during the night.

This action applies to:

0133. Cancel force screensaver to off

Description:

Cancel action 0132. Force screensaver to off and return the screensaver mode to the one defined in the module configuration settings.

Parameters:

None

Feedback behaviour:

LED on when screensaver mode is not forced to off

This action applies to:

0134. Reset absence timer while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the timer of the absence channel is maintained at 0.

Parameters:

None

This action applies to:

0135. Monitor status of initiator

Description:

Make the subject's feedback LED display the status of the initiator. For this action to work, the LED feedback of the subject channel has to be set to Monitoring (in the module configuration settings).

Parameters:

None

Examples:

Example: A push button switches the light in a room. Instead of displaying the status of the light in the room, we want the push button's LED to display the status of another light (eg. the driveway light). In order to do so change the LED feedback setting of the push button to Monitoring, and create an action 0135. Monitor status of initiator with as initiator the driveway light relay, and as subject the push button.

This action applies to:

0136. Comfort/III mode (continuous at long press, temporarily at short press)

Description:

Set the thermostat to comfort mode (when heating) or position III (when cooling). A short press will change the mode only temporarily (during the time set in the module configuration settings), a long press will change the mode until the next action or program step that changes the mode. (If used in program steps, select Long press without release as duration for the program step.)

Parameters:

None

Feedback behaviour:

LED on when thermostat is in corresponding mode

This action applies to:

0137. Day/II mode (continuous at long press, temporarily at short press)

Description:

Set the thermostat to day mode (when heating) or position II (when cooling). A short press will change the mode only temporarily (during the time set in the module configuration settings), a long press will change the mode until the next action or program step that changes the mode. (If used in program steps, select Long press without release as duration for the program step.)

Parameters:

None

Feedback behaviour:

LED on when thermostat is in corresponding mode

This action applies to:

0138. Night/I mode (continuous at long press, temporarily at short press)

Description:

Set the thermostat to night mode (when heating) or position I (when cooling). A short press will change the mode only temporarily (during the time set in the module configuration settings), a long press will change the mode until the next action or program step that changes the mode. (If used in program steps, select Long press without release as duration for the program step.)

Parameters:

None

Feedback behaviour:

LED on when thermostat is in corresponding mode

This action applies to:

0139. Safe/standby mode (continuous at long press, temporarily at short press)

Description:

Set the thermostat to safe mode (when heating) or standby position (when cooling). A short press will change the mode only temporarily (during the time set in the module configuration settings), a long press will change the mode until the next action or program step that changes the mode. (If used in program steps, select Long press without release as duration for the program step.)

Parameters:

None

Feedback behaviour:

LED on when thermostat is in corresponding mode

This action applies to:

0140. Set to mode 1

Description:

Parameters:

  • Duration at short press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: Until next program step

Examples:

This action applies to:

0141. Set to mode 2

Description:

Parameters:

  • Duration at short press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: Until next program step

Examples:

This action applies to:

0142. Set to mode 3

Description:

Parameters:

  • Duration at short press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: Until next program step

Examples:

This action applies to:

0143. Set to mode 4

Description:

Parameters:

  • Duration at short press
    • No action
    • Until next program step
    • Default sleep time
    • 15 min to 45 days
    • Ignore all program steps
    • Default value: Until next program step

Examples:

This action applies to:

02 Dimming

0201. Dim up/down

Description:

Single button control, combining 0204. Dim up and 0207. Dim down. Each time the initiator closes or is pressed, the dimming direction will be opposite from the last one the subject channel has used.

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.

Diagrams:


Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

This action applies to:

0202. Dim at long press, toggle at short press

Description:

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

This action applies to:

0203. Dim at long press, memory or off at short press

Description:

  • long press = 0201. Dim up/down
  • short press = if current dimming value is 0%, go to previous value; if current dimming value is different from 0%, turn off

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

This action applies to:

0204. Dim up

Description:

As long as the initiator is closed (on, pressed), the dimmer keeps dimming up (the dim value increases). For standard operation (dim button) the duration is set to continuous.

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.

See also 0207. Dim down.

Diagrams:


Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

This action applies to:

0205. Dim up at long press, on at short press

Description:

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

This action applies to:

0206. Dim up at long press, memory at short press

Description:

  • long press = 0204. Dim up
  • short press = if current dimming value is different from 0%: no action; if current dimming value is 0%, go to previous value

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

This action applies to:

0207. Dim down

Description:

As long as the initiator is closed (on, pressed), the dimmer keeps dimming down (the dim value decreases). For standard operation (dim button) the duration is set to continuous.

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released.

See also 0204. Dim up.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

This action applies to:

0208. Dim down at long press, off at short press

Description:

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

This action applies to:

0209. Dim to set percent

Parameters:

  • Dim percentage
    • 0 to 100%
    • Default value: 50%

This action applies to:

0210. Dim to set percent over time

Parameters:

  • Dim up/down duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Dim percentage
    • 0 to 100%
    • Default value: 50%

This action applies to:

0211. Turn on gradually

Parameters:

None

This action applies to:

0212. Turn off gradually

Parameters:

None

This action applies to:

0213. Slave (following initiator)

Description:

This action is used for master/slave dimming. Master/slave dimming uses the initiator dimming channel as the master. When dimming the master channel up or down, the slave will follow. But when dimming the slave up or down, the master channel will not follow.

The master must be initiator of this action, and the slave subject.

Don't forget to set the master dimming channel as master in the configuration settings of the dimmer module.

Parameters:

None

This action applies to:

0214. Atmospheric dimvalue

Description:

When the initiator closes or is pressed, the light dims to the set dimming value. This value can be set in percentages ranging from 0% (completely off) to 100% (completely on) in steps of 1%.

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%. The timer is restartable.

The dim up / down duration defines how long it will take to dim gradually from the current percentage to the target percentage.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous
  • Dim up/down duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Dim percentage
    • 0 to 100%
    • Default value: 50%

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

This action applies to:

0215. Multi step dimmer

Description:

A list of dimming values is entered in the dimmer's configuration settings. Every time the initiator closes, the dimmer will go to the next dimming value (similar to consecutively activating dim percentages with a single button, see action 0214. Atmospheric dimvalue).

By entering only two dim values in the list (eg. 0% and 65%), this action can be used as a dim toggle.

If duration is different from continuous, the dimming channel will be switched off after the timer expires. The timer starts to run as soon as the initiator is released or when the dimming channel reaches 100%.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous
  • Dim up/down duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED is off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when a dimming value different from 0% is reached (blinking slowly if duration is different from continuous)

Examples:

With each press on a button, the dimmer cycles through the dimming values 0%, 25%, 50%, 75% and then 0% etc. (the number of steps and their values can be freely configured).

This action applies to:

03 Dim slowly on / dim slowly off

0301. Slow on

Description:

When the initiator closes or is pressed, the dimming channel goes slowly to 100%.

Parameters:

  • Dim up duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED off when dimmer is off (0%), blinks during dimming up or down, and is constantly lit when dimming value different from 0% is reached

Examples:

Slow on.

This action applies to:

0302. Slow on when initiator closes, slow off when initiator opens

Description:

When the initiator closes or is pressed, the dimming channel will go slowly to 100% (see action 0301. Slow on). It will then remain on during duration ('continuous' = until it is switched off). When the initiator is released or opened, or when the timer expires, the dimming channel will go off slowly (see action 0303. Slow off).

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous
  • Dim up duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Dim down duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)

Examples:

Slow on, remain on during a certain time, then slow off.

This action applies to:

0303. Slow off

Description:

When the initiator closes or is pressed, the dimming channel goes slowly to 0%.

Parameters:

  • Dim down duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED always off

This action applies to:

0304. Slow on/off

Description:

When the initiator closes or is pressed, and the dimvalue = 0%, action 0301. Slow on is executed.

When the initiator closes or is pressed, and the dimvalue is different from 0%, action 0303. Slow off is executed.

Parameters:

  • Dim down duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s
  • Dim up duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED always off

This action applies to:

04 Timer

0401. Start timer 1

Parameters:

None

This action applies to:

0402. Toggle timer 1

Parameters:

None

This action applies to:

0403. Start timer 2

Parameters:

None

This action applies to:

0404. Toggle timer 2

Parameters:

None

This action applies to:

0405. Start/stop timer

Description:

When the initiator closes or is pressed, the subject closes and a timer starts to run. The subject opens when the timer expires.

If the initiator is closed while the timer is running, the timer stops (and is reset to zero) and the subject opens.

A short press can start another timer than a long press, provided the initiator is a push button.

Diagrams:


Parameters:

  • Duration at short press
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s
  • Duration at long press
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED on when subject is on, blinks while timer is running (normal blinking for short press, slow blinking for long press)

This action applies to:

0406. Trigger-on-release timer

Description:

When the initiator opens or is released, the subject closes and a timer starts to run. The subject opens when the timer expires. If the initiator is opened while the timer is running, the timer restarts.

Diagrams:


Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED on when subject is on, blinks while timer is running (constantly on if duration = continuous)

This action applies to:

0407. Non-restartable timer

Description:

When the initiator closes or is pressed, the subject closes and a timer starts to run. The subject opens when the timer expires. The timer cannot be restarted: closing the initiator while the timer is running has no effect.

Diagrams:


Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED on when subject is on, blinks while timer is running (constantly on if duration = continuous)

This action applies to:

0408. Start/stop timer

Description:

Similar to 0405. Start/stop timer, but for dimmer channels.

When the initiator closes or is pressed, the subject is turned on (100%), and then turned off (0%) when the timer expires. If the initiator is closed (pressed) while the timer is running, the timer is stopped (and reset to 0) and the subject is turned off (0%).

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 10s

Feedback behaviour:

LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)

This action applies to:

0409. Start/stop timer with slow on/off

Description:

Similar to action 0408. Start/stop timer with adjustable dimming-up and dimming-down durations (see actions 0301. Slow on and 0303. Slow off).

Parameters:

  • Dim down duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s
  • Dim up duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s
  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 10s

Feedback behaviour:

LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)

This action applies to:

0410. Restartable timer

Description:

Similar to 0412. Restartable timer, but for dimmer channels.

When the initiator closes or is pressed, the subject is turned on (100%), and then turned off (0%) when the timer expires. If the initiator is closed (pressed) while the timer is running, the timer is restarted (similar to action 0412. Restartable timer).

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 10s

Feedback behaviour:

LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)

This action applies to:

0411. Restartable timer with slow on/off

Description:

Similar to action 0410. Restartable timer with adjustable dimming-up and dimming-down times (see actions 0301. Slow on and 0303. Slow off).

Parameters:

  • Dim down duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s
  • Dim up duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s
  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 10s

Feedback behaviour:

LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)

This action applies to:

0412. Restartable timer

Description:

When the initiator closes or is pressed, the subject closes and a timer starts to run. The subject opens when the timer expires. The timer can be restarted by closing the initiator while the timer is running.

A short press can start another timer than a long press, provided the initiator is a push button.

Diagrams:


Parameters:

  • Duration at short press
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s
  • Duration at long press
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED on when subject is on, blinks while timer is running (normal blinking for short press, slow blinking for long press)

This action applies to:

0413. Non-restartable timer

Description:

Similar to 0407. Non-restartable timer, but for dimmer channels.

When the initiator closes or is pressed, the subject is turned on (100%) and a timer starts to run. The subject is turned off (0%) when the timer expires. The timer cannot be restarted: closing the initiator while the timer is running has no effect.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 10s

Feedback behaviour:

LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)

This action applies to:

0414. Non-restartable timer with slow on/off

Description:

Similar to action 0413. Non-restartable timer with adjustable dimming-up and dimming-down times (see actions 0301. Slow on and 0303. Slow off).

Parameters:

  • Dim down duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s
  • Dim up duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s
  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 10s

Feedback behaviour:

LED blinks while dimming up or down, blinks slowly while the timer is running (is constantly lit if duration = continuous)

This action applies to:

0415. Start/stop interval timer

Description:

When the initiator closes or is pressed, an interval timer starts to run on the subject (intermittently on and off).

If the initiator is closed while the timer is running, the timer stops (and is reset to zero) and the subject opens.

An interval timer always starts with a pulse, never with a pause.

Diagrams:

Parameters:

  • Total duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 10s
  • Pulse duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 1s
  • Pause duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 1s

Feedback behaviour:

LED on when subject is on, blinks while timer is running (constantly on if duration = continuous)

This action applies to:

0416. Restartable interval timer

Description:

When the initiator closes or is pressed, an interval timer starts to run on the subject (intermittently on and off).

The timer can be restarted by closing the initiator while the timer is running.

An interval timer always starts with a pulse, never with a pause.

Diagrams:

Parameters:

  • Total duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 10s
  • Pulse duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 1s
  • Pause duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 1s

Feedback behaviour:

LED on when subject is on, blinks while timer is running (constantly on if duration = continuous)

This action applies to:

0417. Non-restartable interval timer

Description:

When the initiator closes or is pressed, an interval timer starts to run on the subject (intermittently on and off).

The timer cannot be restarted: closing the initiator while the timer is running has no effect.

An interval timer always starts with a pulse, never with a pause.

Diagrams:


Parameters:

  • Total duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 10s
  • Pulse duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 1s
  • Pause duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 1s

Feedback behaviour:

LED on when subject is on, blinks while timer is running (constantly on if duration = continuous)

This action applies to:

05 Delays

0501. Start/stop delayed on

Description:

When the initiator closes or is pressed, the subject first remains open during the on delay (t1). Then, when the on delay (t1) expires, the subject closes and the timer (t2) starts running; the subject then remains closed until the timer (t2) expires.

Both the on delay (t1) and the timer (t2) are start/stop timers. If the initiator is closed while the on delay (t1) is running, the on delay (t1) stops (and is reset to zero) and the subject remains open. If the initiator is closed while the timer (t2) is running, the timer (t2) stops (and is reset to zero) and the subject opens.

Diagrams:


Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous
  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED on when subject is on, blinks while timers are running (constantly on if duration = continuous)

This action applies to:

0502. Restartable delayed on

Description:

When the initiator closes or is pressed, the subject first remains open during the on delay (t1). Then, when the on delay (t1) expires, the subject closes and the timer (t2) starts running; the subject then remains closed until the timer (t2) expires.

The on delay (t1) can be restarted by closing the initiator.

The timer (t2) cannot be restarted: closing the initiator while the timer (t2) is running has no effect.

Diagrams:


Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous
  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED on when subject is on, blinks while timers are running (constantly on if duration = continuous)

This action applies to:

0503. Non-restartable delayed on

Description:

When the initiator closes or is pressed, the subject first remains open during the on delay (t1). Then, when the on delay (t1) expires, the subject closes and the timer (t2) starts running; the subject then remains closed until the timer (t2) expires.

Nor the on delay (t1), neither the timer (t2) can be restarted: closing the intiator while they are running has no effect.

Diagrams:


Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous
  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED on when subject is on, blinks while timers are running (constantly on if duration = continuous)

This action applies to:

0504. On when initiator closes, delayed off when initiator opens

Description:

When the initiator closes or is pressed, the subject closes (on).

When the initiator opens or is released, a timer begins to run. When the timer expires, the subject opens.

If the initiator is opened while the timer is running, the timer restarts.

Diagrams:


Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running (constantly on if duration = continuous)

This action applies to:

0505. Delayed off only when subject is on

Description:

When the initiator opens or is released, a timer begins to run. When the timer expires, the subject opens.

If the initiator is opened while the timer is running, the timer restarts.

This action is ignored if the subject was open when the initiator opens.

Diagrams:



Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 5s

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running (constantly on if duration = continuous)

This action applies to:

06 Lock / unlock

0601. Lock channel

Description:

When the initiator closes or is pressed, the subject channel is locked.

While a channel is locked, it does not send pressed or released commands.

For advanced users: The actions 0602. Lock channel while initiator is closed and 0603. Lock channel while initiator is open on the one hand, and the result of the actions 0601. Lock channel, 0604. Unlock channel and 0605. Lock/unlock channel on the other hand, are internally treated as a logical OR. Also, an action 0601. Lock channel or 0605. Lock/unlock channel that is started during an action 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open will be memorized and executed after the 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is locked (blinks slowly if duration is different from continuous)

This action applies to:

0602. Lock channel while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the subject channel is locked.

While a channel is locked, it does not send pressed or released commands.

For advanced users: The actions 0602. Lock channel while initiator is closed and 0603. Lock channel while initiator is open on the one hand, and the result of the actions 0601. Lock channel, 0604. Unlock channel and 0605. Lock/unlock channel on the other hand, are internally treated as a logical OR. Also, an action 0601. Lock channel or 0605. Lock/unlock channel that is started during an action 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open will be memorized and executed after the 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Parameters:

None

This action applies to:

0603. Lock channel while initiator is open

Description:

As long as the initiator is open (off, released), the subject channel is locked.

While a channel is locked, it does not send pressed or released commands.

For advanced users: The actions 0602. Lock channel while initiator is closed and 0603. Lock channel while initiator is open on the one hand, and the result of the actions 0601. Lock channel, 0604. Unlock channel and 0605. Lock/unlock channel on the other hand, are internally treated as a logical OR. Also, an action 0601. Lock channel or 0605. Lock/unlock channel that is started during an action 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open will be memorized and executed after the 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Parameters:

None

This action applies to:

0604. Unlock channel

Description:

When the initiator closes or is pressed, the subject channel is unlocked (cfr. 0601. Lock channel).

For advanced users: The actions 0602. Lock channel while initiator is closed and 0603. Lock channel while initiator is open on the one hand, and the result of the actions 0601. Lock channel, 0604. Unlock channel and 0605. Lock/unlock channel on the other hand, are internally treated as a logical OR. Also, an action 0601. Lock channel or 0605. Lock/unlock channel that is started during an action 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open will be memorized and executed after the 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

0605. Lock/unlock channel

Description:

If the subject channel was locked when the initiator closes, it will be unlocked (cfr. 0604. Unlock channel). If the subject channel was unlocked when the initiator closes, it will be locked (cfr. 0601. Lock channel).

The duration parameter only applies to locking.

For advanced users: The actions 0602. Lock channel while initiator is closed and 0603. Lock channel while initiator is open on the one hand, and the result of the actions 0601. Lock channel, 0604. Unlock channel and 0605. Lock/unlock channel on the other hand, are internally treated as a logical OR. Also, an action 0601. Lock channel or 0605. Lock/unlock channel that is started during an action 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open will be memorized and executed after the 0602. Lock channel while initiator is closed or 0603. Lock channel while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is locked (blinks slowly if duration is different from continuous)

This action applies to:

07 Inhibit

0701. Inhibit

Description:

When the initiator closes or is pressed, the subject is inhibited until the inhibit mode is cancelled, or until the duration is expired, or until a forcing action is started (forcing overrides inhibition).

During inhibition mode, the subject will be off (or for blinds: locked to its last position) and will not perform any actions. Inhibited channels keep listening to the bus, but do not react as long as they are inhibited. Eg. running timers will continue to run, and can be started, restarted, stopped etc., but the subject channel will remain off (or locked to its position for blinds) until inhibition mode is cancelled. When cancelling inhibition, the subject will execute the last command that was sent during inhibition mode, or in the absence of such a command, it will return to the state it was in before inhibition.

Forcing off overrides forcing on, which in turn overrides inhibition, which in turn overrides all other actions.

For advanced users: The actions 0702. Inhibit while initiator is closed and 0703. Inhibit while initiator is open on the one hand, and the result of the actions 0701. Inhibit, 0704. Cancel inhibit and 0705. Toggle inhibit on the other hand, are internally treated as a logical OR. Also, an action 0701. Inhibit or 0705. Toggle inhibit that is started during an action 0702. Inhibit while initiator is closed or 0703. Inhibit while initiator is open will be memorized and executed after the 0702. Inhibit while initiator is closed or 0703. Inhibit while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Diagrams:




Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0702. Inhibit while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the subject is inhibited.

During inhibition mode, the subject will be off (or for blinds: locked to its last position) and will not perform any actions. Inhibited channels keep listening to the bus, but do not react as long as they are inhibited. Eg. running timers will continue to run, and can be started, restarted, stopped etc., but the subject channel will remain off (or locked to its position for blinds) until inhibition mode is cancelled. When cancelling inhibition, the subject will execute the last command that was sent during inhibition mode, or in the absence of such a command, it will return to the state it was in before inhibition.

Forcing off overrides forcing on, which in turn overrides inhibition, which in turn overrides all other actions.

For advanced users: The actions 0702. Inhibit while initiator is closed and 0703. Inhibit while initiator is open on the one hand, and the result of the actions 0701. Inhibit, 0704. Cancel inhibit and 0705. Toggle inhibit on the other hand, are internally treated as a logical OR. Also, an action 0701. Inhibit or 0705. Toggle inhibit that is started during an action 0702. Inhibit while initiator is closed or 0703. Inhibit while initiator is open will be memorized and executed after the 0702. Inhibit while initiator is closed or 0703. Inhibit while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Diagrams:


Parameters:

None

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0703. Inhibit while initiator is open

Description:

As long as the initiator is open (off, released), the subject is inhibited.

During inhibition mode, the subject will be off (or for blinds: locked to its last position) and will not perform any actions. Inhibited channels keep listening to the bus, but do not react as long as they are inhibited. Eg. running timers will continue to run, and can be started, restarted, stopped etc., but the subject channel will remain off (or locked to its position for blinds) until inhibition mode is cancelled. When cancelling inhibition, the subject will execute the last command that was sent during inhibition mode, or in the absence of such a command, it will return to the state it was in before inhibition.

Forcing off overrides forcing on, which in turn overrides inhibition, which in turn overrides all other actions.

For advanced users: The actions 0702. Inhibit while initiator is closed and 0703. Inhibit while initiator is open on the one hand, and the result of the actions 0701. Inhibit, 0704. Cancel inhibit and 0705. Toggle inhibit on the other hand, are internally treated as a logical OR. Also, an action 0701. Inhibit or 0705. Toggle inhibit that is started during an action 0702. Inhibit while initiator is closed or 0703. Inhibit while initiator is open will be memorized and executed after the 0702. Inhibit while initiator is closed or 0703. Inhibit while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Diagrams:


Parameters:

None

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0704. Cancel inhibit

Description:

When the initiator closes or is pressed, the inhibition mode on the subject is cancelled (cfr. 0701. Inhibit).

When cancelling inhibition, the subject will execute the last command that was sent during inhibition mode, or in the absence of such a command, it will return to the state it was in before inhibition.

For advanced users: The actions 0702. Inhibit while initiator is closed and 0703. Inhibit while initiator is open on the one hand, and the result of the actions 0701. Inhibit, 0704. Cancel inhibit and 0705. Toggle inhibit on the other hand, are internally treated as a logical OR. Also, an action 0701. Inhibit or 0705. Toggle inhibit that is started during an action 0702. Inhibit while initiator is closed or 0703. Inhibit while initiator is open will be memorized and executed after the 0702. Inhibit while initiator is closed or 0703. Inhibit while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

0705. Toggle inhibit

Description:

When the initiator closes or is pressed, and the subject was in 0701. Inhibit mode, it will return to normal mode (not 0701. Inhibit). If it was in normal mode, it will be put in 0701. Inhibit mode. (For details about inhibition mode cfr. 0701. Inhibit).

The duration parameter only applies to the inhibition mode, not to the cancelling of the inhibition mode.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0706. Inhibit preset up

Description:

Same as action 0701. Inhibit but the blind will go completely up when inhibited.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0707. Inhibit but preset up while initiator is closed

Description:

Same as action 0702. Inhibit while initiator is closed but the blind will go completely up when inhibited.

Parameters:

None

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0708. Inhibit but preset up while initiator is open

Description:

Same as action 0703. Inhibit while initiator is open but the blind will go completely up when inhibited.

Parameters:

None

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0709. Cancel inhibit but preset up

Description:

Cancel 0706. Inhibit preset up

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

0710. Toggle inhibit but preset up

Description:

When the initiator closes or is pressed, and the subject was in 0706. Inhibit preset up mode, it will return to normal mode (not 0706. Inhibit preset up). If it was in normal mode, it will be put in 0706. Inhibit preset up mode. (For details about inhibition mode cfr. 0701. Inhibit).

The duration parameter only applies to the inhibition mode, not to the cancelling of the inhibition mode.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0711. Inhibit preset down

Description:

Same as action 0701. Inhibit but the blind will go completely down when inhibited.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0712. Inhibit but preset down while initiator is closed

Description:

Same as action 0702. Inhibit while initiator is closed but the blind will go completely down when inhibited.

Parameters:

None

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0713. Inhibit but preset down while initiator is open

Description:

Same as action 0703. Inhibit while initiator is open but the blind will go completely down when inhibited.

Parameters:

None

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

0714. Cancel inhibit but preset down

Description:

Cancel 0711. Inhibit preset down

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

0715. Toggle inhibit but preset down

Description:

When the initiator closes or is pressed, and the subject was in 0711. Inhibit preset down mode, it will return to normal mode (not 0711. Inhibit preset down). If it was in normal mode, it will be put in 0711. Inhibit preset down mode. (For details about inhibition mode cfr. 0701. Inhibit).

The duration parameter only applies to the inhibition mode, not to the cancelling of the inhibition mode.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is inhibited (blinks slowly if duration is different from continuous)

This action applies to:

08 Forced

0801. Forced on

Description:

When the initiator closes or is pressed, the subject is switched on and goes into forced mode. It remains forced on until the forced mode is cancelled or until the timer expires. All timers that were already running will be stopped.

A channel that is 'forced on' ignores everything that happens on the bus, except 'forced off' actions (which override 'forced on'), and cancelling the 'forced on' mode. When the 'forced on' mode expires, the channel will be switched off and return to normal mode. All signals sent during the forced mode will be ignored.

Forcing off overrides forcing on, which in turn overrides inhibition, which in turn overrides all other actions.

For advanced users: The actions 0802. Forced on while initiator is closed and 0803. Forced on while initiator is open on the one hand, and the result of the actions 0801. Forced on, 0804. Cancel forced on and 0805. Toggle forced on on the other hand, are internally treated as a logical OR. Also, an action 0801. Forced on or 0805. Toggle forced on that is started during an action 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open will be memorized and executed after the 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Diagrams:

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is forced on (blinks slowly if duration is different from continuous)

This action applies to:

0802. Forced on while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the subject is switched on and goes into forced mode. It remains forced on until the initiator opens. All timers that were already running will be stopped.

A channel that is 0802. Forced on while initiator is closed ignores everything that happens on the bus, except 'forced off' actions (which override 'forced on'). When the 'forced on' mode expires, the channel will be switched off and return to normal mode. All signals sent during the forced mode will be ignored.

Forcing off overrides forcing on, which in turn overrides inhibition, which in turn overrides all other actions.

For advanced users: The actions 0802. Forced on while initiator is closed and 0803. Forced on while initiator is open on the one hand, and the result of the actions 0801. Forced on, 0804. Cancel forced on and 0805. Toggle forced on on the other hand, are internally treated as a logical OR. Also, an action 0801. Forced on or 0805. Toggle forced on that is started during an action 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open will be memorized and executed after the 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Diagrams:

Parameters:

None

This action applies to:

0803. Forced on while initiator is open

Description:

As long as the initiator is open (off, released), the subject is switched on and goes into forced mode. It remains forced on until the initiator closes. All timers that were already running will be stopped.

A channel that is 0803. Forced on while initiator is open ignores everything that happens on the bus, except 'forced off' actions (which override 'forced on'). When the 'forced on' mode expires, the channel will be switched off and return to normal mode. All signals sent during the forced mode will be ignored.

Forcing off overrides forcing on, which in turn overrides inhibition, which in turn overrides all other actions.

For advanced users: The actions 0802. Forced on while initiator is closed and 0803. Forced on while initiator is open on the one hand, and the result of the actions 0801. Forced on, 0804. Cancel forced on and 0805. Toggle forced on on the other hand, are internally treated as a logical OR. Also, an action 0801. Forced on or 0805. Toggle forced on that is started during an action 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open will be memorized and executed after the 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Diagrams:

Parameters:

None

This action applies to:

0804. Cancel forced on

Description:

Cancel 0801. Forced on. After cancelling "forced on", the subject will be off.

For advanced users: The actions 0802. Forced on while initiator is closed and 0803. Forced on while initiator is open on the one hand, and the result of the actions 0801. Forced on, 0804. Cancel forced on and 0805. Toggle forced on on the other hand, are internally treated as a logical OR. Also, an action 0801. Forced on or 0805. Toggle forced on that is started during an action 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open will be memorized and executed after the 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Parameters:

None

This action applies to:

0805. Toggle forced on

Description:

When the initiator closes or is pressed, and the subject was in 0801. Forced on mode, it will return to normal mode (not 0801. Forced on). If it was in normal mode, it will be put in 0801. Forced on mode. (For details about forced mode cfr. 0801. Forced on).

The duration parameter only applies to the forced mode, not to the cancelling of the forced mode.

For advanced users: The actions 0802. Forced on while initiator is closed and 0803. Forced on while initiator is open on the one hand, and the result of the actions 0801. Forced on, 0804. Cancel forced on and 0805. Toggle forced on on the other hand, are internally treated as a logical OR. Also, an action 0801. Forced on or 0805. Toggle forced on that is started during an action 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open will be memorized and executed after the 0802. Forced on while initiator is closed or 0803. Forced on while initiator is open action is over. If it is started with a timer, the remaining part of the timer will be executed.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is forced on (blinks slowly if duration is different from continuous)

This action applies to:

0806. Forced off

Description:

When the initiator closes or is pressed, the subject is switched off and goes into forced mode. It remains forced off until the forced mode is cancelled or until the timer expires. All timers that were already running will be stopped.

A channel that is 0806. Forced off ignores everything that happens on the bus, except cancelling the 'forced off' mode. When the 'forced off' mode expires, the channel will be off (in normal mode, not forced). All signals sent during the forced mode will be ignored.

Forcing off overrides forcing on, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is forced off (blinks slowly if duration is different from continuous)

This action applies to:

0807. Forced off while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the subject is switched off and goes into forced mode. It remains forced off until the initiator opens. All timers that were already running will be stopped.

A channel that is 0807. Forced off while initiator is closed ignores everything that happens on the bus. When the 'forced off' mode expires, the module will remain switched off and return to normal mode. All signals sent during the forced mode will be ignored.

Forcing off overrides forcing on, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED on while subject is forced off (blinks slowly if duration is different from continuous)

This action applies to:

0808. Forced off while initiator is open

Description:

As long as the initiator is open (off, released), the subject is switched off and goes into forced mode. It remains forced off until the initiator closes. All timers that were already running will be stopped.

A channel that is 0808. Forced off while initiator is open ignores everything that happens on the bus. When the 'forced off' mode expires, the module will remain switched off and return to normal mode. All signals sent during the forced mode will be ignored.

Forcing off overrides forcing on, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED on while subject is forced off (blinks slowly if duration is different from continuous)

This action applies to:

0809. Cancel forced off

Description:

Cancel 0806. Forced off

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

0810. Toggle forced off

Description:

When the initiator closes or is pressed, and the subject was in 0806. Forced off mode, it will return to normal mode (not 0806. Forced off). If it was in normal mode, it will be put in 0806. Forced off mode. (For details about forced mode cfr. 0806. Forced off).

The duration parameter only applies to the forced mode, not to the cancelling of the forced mode.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is forced off (blinks slowly if duration is different from continuous)

This action applies to:

0811. Forced up

Description:

When the initiator closes or is pressed, the blind will go up, and remain forced up until the timer expires, or until the forced up mode is cancelled (0814. Cancel forced up). If the forced up is cancelled while the blind is going up, the blind will go up completely (not forced).

Forcing to current position overrides forcing up, which overrides forcing down, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED blinks while the blind goes up, and is constantly lit when completely up

This action applies to:

0812. Forced up while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the blind will remain forced up. If the initiator opens while the blind is going up, the blind will go up completely (not forced).

Forcing to current position overrides forcing up, which overrides forcing down, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes up, and is constantly lit when completely up

This action applies to:

0813. Forced up while initiator is open

Description:

As long as the initiator is open (off, released), the blind will remain forced up. If the initiator closes while the blind is going up, the blind will go up completely (not forced).

Forcing to current position overrides forcing up, which overrides forcing down, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes up, and is constantly lit when completely up

This action applies to:

0814. Cancel forced up

Description:

Cancel 0811. Forced up

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

0815. Toggle forced up

Description:

When the initiator closes or is pressed, and the subject was in 0811. Forced up mode, it will return to normal mode (not 0811. Forced up). If it was in normal mode, it will be put in 0811. Forced up mode. (For details about forced mode cfr. 0811. Forced up).

The duration parameter only applies to the forced mode, not to the cancelling of the forced mode.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED blinks while the blind goes up, and is constantly lit when completely up

This action applies to:

0816. Forced down

Description:

When the initiator closes or is pressed, the blind will go down, and remain forced down until the timer expires, or until the forced down mode is cancelled (0814. Cancel forced up). If the forced down is cancelled while the blind is going down, the blind will go down completely (not forced).

Forcing to current position overrides forcing up, which overrides forcing down, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED blinks while the blind goes down, and is constantly lit when completely down

This action applies to:

0817. Forced down while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the blind will remain forced down. If the initiator opens while the blind is going down, the blind will go down completely (not forced).

Forcing to current position overrides forcing up, which overrides forcing down, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes down, and is constantly lit when completely down

This action applies to:

0818. Forced down while initiator is open

Description:

As long as the initiator is open (off, released), the blind will remain forced down. If the initiator closes while the blind is going down, the blind will go down completely (not forced).

Forcing to current position overrides forcing up, which overrides forcing down, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes down, and is constantly lit when completely down

This action applies to:

0819. Cancel forced down

Description:

Cancel 0816. Forced down

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

0820. Toggle forced down

Description:

When the initiator closes or is pressed, and the subject was in 0816. Forced down mode, it will return to normal mode (not 0816. Forced down). If it was in normal mode, it will be put in 0816. Forced down mode. (For details about forced mode cfr. 0816. Forced down).

The duration parameter only applies to the forced mode, not to the cancelling of the forced mode.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED blinks while the blind goes down, and is constantly lit when completely down

This action applies to:

0821. Force to current position

Description:

When the initiator closes or is pressed, the blind channel will remain fixed at its current position and go into forced mode. The forced mode will remain active until the timer expires, or until it is cancelled by 0824. Cancel force to current position)

Forcing to current position overrides forcing up, which overrides forcing down, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is forced off (blinks slowly if duration is different from continuous)

This action applies to:

0822. Force to current position while initiator is closed

Description:

As long as the initiator is closed (on, pressed), the blind channel will remain fixed at its current position and go into forced mode.

Forcing to current position overrides forcing up, which overrides forcing down, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED on while subject is forced off (blinks slowly if duration is different from continuous)

This action applies to:

0823. Force to current position while initiator is open

Description:

As long as the initiator is open (off, released), the blind channel will remain fixed at its current position and go into forced mode.

Forcing to current position overrides forcing up, which overrides forcing down, which in turn overrides inhibition, which in turn overrides all other actions.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED on while subject is forced off (blinks slowly if duration is different from continuous)

This action applies to:

0824. Cancel force to current position

Description:

Cancel 0821. Force to current position

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

0825. Force/cancel force to current position

Description:

When the initiator closes or is pressed, and the subject was in 0821. Force to current position mode, it will return to normal mode (not 0821. Force to current position). If it was in normal mode, it will be put in 0821. Force to current position mode. (For details about forced mode cfr. 0821. Force to current position).

The duration parameter only applies to the forced mode, not to the cancelling of the forced mode.

See also actions 0801. Forced on to 0805. Toggle forced on for more information on forcing.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on while subject is forced off (blinks slowly if duration is different from continuous)

This action applies to:

09 Programs

0901. Enable program steps for this channel

Description:

When the initiator closes or is pressed, program steps for the subject channel are enabled. See also 0902. Disable program steps for this channel.

Parameters:

None

This action applies to:

0902. Disable program steps for this channel

Description:

When the initiator closes or is pressed, program steps for the subject channel are disabled. See also 0901. Enable program steps for this channel.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

0903. Disable program steps for this channel while initiator is closed

Description:

As long as the initiator is closed (on, pressed), program steps for the subject channel are disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

0904. Disable program steps for this channel while initiator is open

Description:

As long as the initiator is open (off, released), program steps for the subject channel are disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

0905. Toggle program steps for this channel

Description:

If program steps for the subject were enabled when the initiator closes, they will be disabled. If program steps for the subject were disabled when the initiator closes, they will be enabled.

Parameters:

  • Duration
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: Continuous

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

0906. Select no program

Description:

When the initiator closes or is pressed, the active program on the module will be set to 'no program'. In other words, all programs are deactivated.

Parameters:

None

Feedback behaviour:

LED on when no program is selected

This action applies to:

0907. Select program 1

Description:

When the initiator closes or is pressed, the active program on the module will be set to program 1.

Parameters:

None

Feedback behaviour:

LED on when program 1 is enabled

This action applies to:

0908. Select program 2

Description:

When the initiator closes or is pressed, the active program on the module will be set to program 2.

Parameters:

None

Feedback behaviour:

LED on when program 2 is enabled

This action applies to:

0909. Select program 3

Description:

When the initiator closes or is pressed, the active program on the module will be set to program 3.

Parameters:

None

Feedback behaviour:

LED on when program 3 is enabled

This action applies to:

0910. Toggle program 1

Description:

If the active program was set to 'program 1' when the initiator closes, it will be set to 'no program'. If the active program was anything else than program 1, it will be set to program 1.

Parameters:

None

Feedback behaviour:

LED on when program 1 is enabled

This action applies to:

0911. Toggle program 2

Description:

If the active program was set to 'program 2' when the initiator closes, it will be set to 'no program'. If the active program was anything else than program 2, it will be set to program 2.

Parameters:

None

Feedback behaviour:

LED on when program 2 is enabled

This action applies to:

0912. Toggle program 3

Description:

If the active program was set to 'program 3' when the initiator closes, it will be set to 'no program'. If the active program was anything else than program 3, it will be set to program 3.

Parameters:

None

Feedback behaviour:

LED on when program 3 is enabled

This action applies to:

0913. Enable alarm/sunrise/sunset

Description:

When the initiator closes or is pressed, all program steps on the module related to alarm/sunrise /sunset will be enabled.

Parameters:

  • Activate program steps using
    • Alarm 1
    • Alarm 2
    • Sunrise
    • Sunset
    • Default value: Alarm 1

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

0914. Enable alarm/sunrise/sunset while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to alarm/sunrise /sunset will be enabled.

Parameters:

  • Activate program steps using
    • Alarm 1
    • Alarm 2
    • Sunrise
    • Sunset
    • Default value: Alarm 1

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

0915. Enable alarm/sunrise/sunset while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to alarm/sunrise /sunset will be enabled.

Parameters:

  • Activate program steps using
    • Alarm 1
    • Alarm 2
    • Sunrise
    • Sunset
    • Default value: Alarm 1

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

0916. Disable alarm/sunrise/sunset

Description:

When the initiator closes or is pressed, all program steps on the module related to alarm/sunrise /sunset will be disabled.

Parameters:

  • Activate program steps using
    • Alarm 1
    • Alarm 2
    • Sunrise
    • Sunset
    • Default value: Alarm 1

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

0917. Disable alarm/sunrise/sunset while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to alarm/sunrise /sunset will be disabled.

Parameters:

  • Activate program steps using
    • Alarm 1
    • Alarm 2
    • Sunrise
    • Sunset
    • Default value: Alarm 1

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

0918. Disable alarm/sunrise/sunset while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to alarm/sunrise /sunset will be disabled.

Parameters:

  • Activate program steps using
    • Alarm 1
    • Alarm 2
    • Sunrise
    • Sunset
    • Default value: Alarm 1

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

0919. Toggle alarm/sunrise/sunset

Description:

If program steps related to alarm/sunrise /sunset were disabled when the initiator closes, they will be enabled on the module.

If program steps related to alarm/sunrise /sunset were enabled, they will be disabled.

Parameters:

  • Activate program steps using
    • Alarm 1
    • Alarm 2
    • Sunrise
    • Sunset
    • Default value: Alarm 1

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

10 Clock alarms

1001. Enable Clock Alarm 1 related program steps

Description:

When the initiator closes or is pressed, all program steps on the module related to clock alarm 1 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1002. Enable Clock Alarm 1 related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to clock alarm 1 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1003. Enable Clock Alarm 1 related program steps while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to clock alarm 1 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1004. Disable Clock Alarm 1 related program steps

Description:

When the initiator closes or is pressed, all program steps on the module related to clock alarm 1 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1005. Disable Clock Alarm 1 related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to clock alarm 1 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1006. Disable Clock Alarm 1 related program steps while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to clock alarm 1 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1007. Toggle Clock Alarm 1 related program steps

Description:

If program steps related to clock alarm 1 were disabled when the initiator closes, they will be enabled on the module.

If program steps related to clock alarm 1 were enabled, they will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1008. Enable Clock Alarm 2 related program steps

Description:

When the initiator closes or is pressed, all program steps on the module related to clock alarm 2 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1009. Enable Clock Alarm 2 related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to clock alarm 2 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1010. Enable Clock Alarm 2 related program steps while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to clock alarm 2 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1011. Disable Clock Alarm 2 related program steps

Description:

When the initiator closes or is pressed, all program steps on the module related to clock alarm 2 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1012. Disable Clock Alarm 2 related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to clock alarm 2 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1013. Disable Clock Alarm 2 related program steps while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to clock alarm 2 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1014. Toggle Clock Alarm 2 related program steps

Description:

If program steps related to clock alarm 2 were disabled when the initiator closes, they will be enabled on the module.

If program steps related to clock alarm 2 were enabled, they will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1015. Enable Clock Alarm 1 related program steps

Description:

When the initiator closes or is pressed, rolling up and down at clock alarm 1 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1016. Enable Clock Alarm 1 related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), rolling up and down at clock alarm 1 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1017. Enable Clock Alarm 1 related program steps while initiator is open

Description:

As long as the initiator is open (off, released), rolling up and down at clock alarm 1 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1018. Disable Clock Alarm 1 related program steps

Description:

When the initiator closes or is pressed, rolling up and down at clock alarm 1 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1019. Disable Clock Alarm 1 related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), rolling up and down at clock alarm 1 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1020. Disable Clock Alarm 1 related program steps while initiator is open

Description:

As long as the initiator is open (off, released), rolling up and down at clock alarm 1 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1021. Toggle Clock Alarm 1 related program steps

Description:

If rolling up/down at clock alarm 1 were disabled when the initiator closes, they will be enabled on the module.

If rolling up/down at clock alarm 1 were enabled, they will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1022. Enable Clock Alarm 2 related program steps

Description:

When the initiator closes or is pressed, rolling up and down at clock alarm 2 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1023. Enable Clock Alarm 2 related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), rolling up and down at clock alarm 2 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1024. Enable Clock Alarm 2 related program steps while initiator is open

Description:

As long as the initiator is open (off, released), rolling up and down at clock alarm 2 will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1025. Disable Clock Alarm 2 related program steps

Description:

When the initiator closes or is pressed, rolling up and down at clock alarm 2 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1026. Disable Clock Alarm 2 related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), rolling up and down at clock alarm 2 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1027. Disable Clock Alarm 2 related program steps while initiator is open

Description:

As long as the initiator is open (off, released), rolling up and down at clock alarm 2 will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1028. Toggle Clock Alarm 2 related program steps

Description:

If rolling up/down at clock alarm 2 were disabled when the initiator closes, they will be enabled on the module.

If rolling up/down at clock alarm 2 were enabled, they will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

11 Sunrise / Sunset

1101. Enable Sunrise related program steps

Description:

When the initiator closes or is pressed, all program steps on the module related to sunrise will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1102. Enable Sunrise related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to sunrise will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1103. Enable Sunrise related program steps while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to sunrise will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1104. Disable Sunrise related program steps

Description:

When the initiator closes or is pressed, all program steps on the module related to sunrise will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1105. Disable Sunrise related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to sunrise will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1106. Disable Sunrise related program steps while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to sunrise will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1107. Toggle Sunrise related program steps

Description:

If program steps related to sunrise were disabled when the initiator closes, they will be enabled on the module.

If program steps related to sunrise were enabled, they will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1108. Enable Sunset related program steps

Description:

When the initiator closes or is pressed, all program steps on the module related to sunset will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1109. Enable Sunset related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to sunset will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1110. Enable Sunset related program steps while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to sunset will be enabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1111. Disable Sunset related program steps

Description:

When the initiator closes or is pressed, all program steps on the module related to sunset will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1112. Disable Sunset related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), all program steps on the module related to sunset will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1113. Disable Sunset related program steps while initiator is open

Description:

As long as the initiator is open (off, released), all program steps on the module related to sunset will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are disabled

This action applies to:

1114. Toggle Sunset related program steps

Description:

If program steps related to sunset were disabled when the initiator closes, they will be enabled on the module.

If program steps related to sunset were enabled, they will be disabled.

Parameters:

None

Feedback behaviour:

LED on when program steps are enabled

This action applies to:

1115. Enable sunrise related program steps

Description:

When the initiator closes or is pressed, rolling up and down at sunrise will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1116. Enable sunrise related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), rolling up and down at sunrise will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1117. Enable sunrise related program steps while initiator is open

Description:

As long as the initiator is open (off, released), rolling up and down at sunrise will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1118. Disable sunrise related program steps

Description:

When the initiator closes or is pressed, rolling up and down at sunrise will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1119. Disable sunrise related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), rolling up and down at sunrise will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1120. Disable sunrise related program steps while initiator is open

Description:

As long as the initiator is open (off, released), rolling up and down at sunrise will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1121. Toggle sunrise related program steps

Description:

If rolling up/down at sunrise were disabled when the initiator closes, they will be enabled on the module.

If rolling up/down at sunrise were enabled, they will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1122. Enable sunset related program steps

Description:

When the initiator closes or is pressed, rolling up and down at sunrise will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1123. Enable sunset related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), rolling up and down at sunrise will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1124. Enable sunset related program steps while initiator is open

Description:

As long as the initiator is open (off, released), rolling up and down at sunrise will be enabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

1125. Disable sunset related program steps

Description:

When the initiator closes or is pressed, rolling up and down at sunrise will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1126. Disable sunset related program steps while initiator is closed

Description:

As long as the initiator is closed (on, pressed), rolling up and down at sunrise will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1127. Disable sunset related program steps while initiator is open

Description:

As long as the initiator is open (off, released), rolling up and down at sunrise will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down are disabled

This action applies to:

1128. Toggle sunset related program steps

Description:

If rolling up/down at sunrise were disabled when the initiator closes, they will be enabled on the module.

If rolling up/down at sunrise were enabled, they will be disabled.

Parameters:

None

Feedback behaviour:

LED on when rolling up/down enabled

This action applies to:

12 Disable timer

1201. On with timers disabled

Description:

When the initiator closes or is pressed, the subject is switched on and the timers on the subject are blocked.

A blocked timer is stopped and reset to 0. As long as the timers are blocked, they cannot be started. Blocked timers can be released by using one of the 'on' or 'off' actions without timer blocking (eg. 0101. On, 0102. Off, 0103. Toggle, 0104. Momentary (follow)).

Parameters:

None

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running

This action applies to:

1202. On with timers disabled at short press

Description:

1203. On with timers disabled at long press

Description:

Parameters:

None

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running

This action applies to:

1204. Off with timers disabled

Description:

When the initiator closes or is pressed, the subject is switched off and the timers on the subject are blocked.

A blocked timer is stopped and reset to 0. As long as the timers are blocked, they cannot be started. Blocked timers can be released by using one of the 'on' or 'off' actions without timer blocking (eg. 0101. On, 0102. Off, 0103. Toggle, 0104. Momentary (follow)).

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

1205. Off with timers disabled at short press

Description:

1206. Off with timers disabled at long press

Description:

Parameters:

None

Feedback behaviour:

LED always off

This action applies to:

1207. On with timers disabled/off

Description:

If the subject was off when the initiator closes or is pressed, 1201. On with timers disabled will be executed.

If the subject was on when the initiator closes or is pressed, 0102. Off will be executed (and blocked timers will be released).

Parameters:

None

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running

This action applies to:

1208. On with timers disabled/off at short press

Description:

  • If the subject was off when the initiator closes or is pressed,
  • If the subject was on when the initiator closes or is pressed, short press or long press will execute 0102. Off

Parameters:

None

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running

This action applies to:

1209. On with timers disabled/off at long press

Description:

  • If the subject was off when the initiator closes or is pressed,
  • If the subject was on when the initiator closes or is pressed, short press or long press will execute 0102. Off

Parameters:

None

Feedback behaviour:

LED on when subject is closed (on), blinking while timer is running

This action applies to:

13 Mode selection

1301. Deselect mode

Description:

For more information on modes for blind channels, cfr. action 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED on when subject is in normal mode (modes 1, 2 and 3 disabled)

This action applies to:

1302. Deselect mode when initiator opens

Description:

For more information on modes for blind channels, cfr. action 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED on when subject is in normal mode (modes 1, 2 and 3 disabled)

This action applies to:

1303. Select mode 1

Description:

When the initiator closes or is pressed, the subject is set to mode 1. See the table below for an overview of which actions are executed in which mode.

Actions and modes for blind channels
normal actions actions for mode 1 actions for mode 2 actions for mode 3
normal mode
mode 1
mode 2
mode 3

Parameters:

None

Feedback behaviour:

LED on when mode 1 is selected on subject

This action applies to:

1304. Select mode 1 when initiator opens

Description:

When the initiator opens or is released, the subject is set to mode 1. See the table below for an overview of which actions are executed in which mode.

Actions and modes for blind channels
normal actions actions for mode 1 actions for mode 2 actions for mode 3
normal mode
mode 1
mode 2
mode 3

Parameters:

None

Feedback behaviour:

LED on when mode 1 is selected on subject

This action applies to:

1305. Toggle mode 1

Description:

If the subject was not in mode 1 when the initiator closes, it will be set to mode 1. If the subject was in mode 1, it will be set to normal mode.

See 1303. Select mode 1, 1306. Select mode 2 and 1309. Select mode 3 for more info on modes.

Parameters:

None

Feedback behaviour:

LED on when mode 1 is selected on subject

This action applies to:

1306. Select mode 2

Description:

When the initiator closes or is pressed, the subject is set to mode 2. See the table below for an overview of which actions are executed in which mode.

Actions and modes for blind channels
normal actions actions for mode 1 actions for mode 2 actions for mode 3
normal mode
mode 1
mode 2
mode 3

Parameters:

None

Feedback behaviour:

LED on when mode 2 is selected on subject

This action applies to:

1307. Select mode 2 when initiator opens

Description:

When the initiator opens or is released, the subject is set to mode 2. See the table below for an overview of which actions are executed in which mode.

Actions and modes for blind channels
normal actions actions for mode 1 actions for mode 2 actions for mode 3
normal mode
mode 1
mode 2
mode 3

Parameters:

None

Feedback behaviour:

LED on when mode 2 is selected on subject

This action applies to:

1308. Toggle mode 2

Description:

If the subject was not in mode 2 when the initiator closes, it will be set to mode 2. If the subject was in mode 2, it will be set to normal mode.

See 1303. Select mode 1, 1306. Select mode 2 and 1309. Select mode 3 for more info on modes.

Parameters:

None

Feedback behaviour:

LED on when mode 2 is selected on subject

This action applies to:

1309. Select mode 3

Description:

When the initiator closes or is pressed, the subject is set to mode 3. See the table below for an overview of which actions are executed in which mode.

Actions and modes for blind channels
normal actions actions for mode 1 actions for mode 2 actions for mode 3
normal mode
mode 1
mode 2
mode 3

Parameters:

None

Feedback behaviour:

LED on when mode 3 is selected on subject

This action applies to:

1310. Select mode 3 when initiator opens

Description:

When the initiator opens or is released, the subject is set to mode 3. See the table below for an overview of which actions are executed in which mode.

Actions and modes for blind channels
normal actions actions for mode 1 actions for mode 2 actions for mode 3
normal mode
mode 1
mode 2
mode 3

Parameters:

None

Feedback behaviour:

LED on when mode 3 is selected on subject

This action applies to:

1311. Toggle mode 3

Description:

If the subject was not in mode 3 when the initiator closes, it will be set to mode 3. If the subject was in mode 3, it will be set to normal mode.

See 1303. Select mode 1, 1306. Select mode 2 and 1309. Select mode 3 for more info on modes.

Parameters:

None

Feedback behaviour:

LED on when mode 3 is selected on subject

This action applies to:

14 Actions in mode 1

1401. Up, only in mode 1

Description:

Same as action 0106. Up, but this action will only be executed if the subject module is set to mode 1.

For more information about modes, see 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes up, and is constantly lit when completely up

This action applies to:

1402. Immediately up, only in mode 1

Description:

Same as action 0109. Immediately up, but this action will only be executed if the subject module is set to mode 1.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes up, and is constantly lit when completely up

This action applies to:

1403. Immediately up when initiator opens, only in mode 1

Description:

Same as action 0108. Immediately up when initiator opens, but this action will only be executed if the subject module is set to mode 1.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes up, and is constantly lit when completely up

This action applies to:

1404. Down, only in mode 1

Description:

Same as action 0110. Down, but this action will only be executed if the subject module is set to mode 1.

For more information about modes, see 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes down, and is constantly lit when completely down

This action applies to:

1405. Immediately down, only in mode 1

Description:

Same as action 0113. Immediately down, but this action will only be executed if the subject module is set to mode 1.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes down, and is constantly lit when completely down

This action applies to:

1406. Immediately down when initiator opens, only in mode 1

Description:

Same as action 0112. Immediately down when initiator opens, but this action will only be executed if the subject module is set to mode 1.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes down, and is constantly lit when completely down

This action applies to:

1407. Up/down, only in mode 1

Description:

Same as action 0114. Up/down, but this action will only be executed if the subject module is set to mode 1.

For more information about modes, see 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED blinks while the blind moves, is off when the blind is completely up and is constantly lit when completely down

This action applies to:

1408. Go to position, only in mode 1

Description:

Same as action 0115. Go to position, but this action will only be executed if the subject module is set to mode 1.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Position
    • 0% (compl. up) to 100% (compl. down)
    • Default value: 50%

Feedback behaviour:

LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position

This action applies to:

1409. Go to position when initiator opens, only in mode 1

Description:

Same as action 0116. Go to position when initiator opens, but this action will only be executed if the subject module is set to mode 1.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Position
    • 0% (compl. up) to 100% (compl. down)
    • Default value: 50%

Feedback behaviour:

LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position

This action applies to:

15 Actions in mode 2

1501. Up, only in mode 2

Description:

Same as action 0106. Up, but this action will only be executed if the subject module is set to mode 2.

For more information about modes, see 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes up, and is constantly lit when completely up

This action applies to:

1502. Immediately up, only in mode 2

Description:

Same as action 0109. Immediately up, but this action will only be executed if the subject module is set to mode 2.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes up, and is constantly lit when completely up

This action applies to:

1503. Immediately up when initiator opens, only in mode 2

Description:

Same as action 0108. Immediately up when initiator opens, but this action will only be executed if the subject module is set to mode 2.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes up, and is constantly lit when completely up

This action applies to:

1504. Down, only in mode 2

Description:

Same as action 0110. Down, but this action will only be executed if the subject module is set to mode 2.

For more information about modes, see 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes down, and is constantly lit when completely down

This action applies to:

1505. Immediately down, only in mode 2

Description:

Same as action 0113. Immediately down, but this action will only be executed if the subject module is set to mode 2.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes down, and is constantly lit when completely down

This action applies to:

1506. Immediately down when initiator opens, only in mode 2

Description:

Same as action 0112. Immediately down when initiator opens, but this action will only be executed if the subject module is set to mode 2.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes down, and is constantly lit when completely down

This action applies to:

1507. Up/down, only in mode 2

Description:

Same as action 0114. Up/down, but this action will only be executed if the subject module is set to mode 2.

For more information about modes, see 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED blinks while the blind moves, is off when the blind is completely up and is constantly lit when completely down

This action applies to:

1508. Go to position, only in mode 2

Description:

Same as action 0115. Go to position, but this action will only be executed if the subject module is set to mode 2.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Position
    • 0% (compl. up) to 100% (compl. down)
    • Default value: 50%

Feedback behaviour:

LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position

This action applies to:

1509. Go to position when initiator opens, only in mode 2

Description:

Same as action 0116. Go to position when initiator opens, but this action will only be executed if the subject module is set to mode 2.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Position
    • 0% (compl. up) to 100% (compl. down)
    • Default value: 50%

Feedback behaviour:

LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position

This action applies to:

16 Actions in mode 3

1601. Up, only in mode 3

Description:

Same as action 0106. Up, but this action will only be executed if the subject module is set to mode 3.

For more information about modes, see 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes up, and is constantly lit when completely up

This action applies to:

1602. Immediately up, only in mode 3

Description:

Same as action 0109. Immediately up, but this action will only be executed if the subject module is set to mode 3.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes up, and is constantly lit when completely up

This action applies to:

1603. Immediately up when initiator opens, only in mode 3

Description:

Same as action 0108. Immediately up when initiator opens, but this action will only be executed if the subject module is set to mode 3.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes up, and is constantly lit when completely up

This action applies to:

1604. Down, only in mode 3

Description:

Same as action 0110. Down, but this action will only be executed if the subject module is set to mode 3.

For more information about modes, see 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED blinks while the blind goes down, and is constantly lit when completely down

This action applies to:

1605. Immediately down, only in mode 3

Description:

Same as action 0113. Immediately down, but this action will only be executed if the subject module is set to mode 3.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes down, and is constantly lit when completely down

This action applies to:

1606. Immediately down when initiator opens, only in mode 3

Description:

Same as action 0112. Immediately down when initiator opens, but this action will only be executed if the subject module is set to mode 3.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)

Feedback behaviour:

LED blinks during on delay and while the blind goes down, and is constantly lit when completely down

This action applies to:

1607. Up/down, only in mode 3

Description:

Same as action 0114. Up/down, but this action will only be executed if the subject module is set to mode 3.

For more information about modes, see 1303. Select mode 1.

Parameters:

None

Feedback behaviour:

LED blinks while the blind moves, is off when the blind is completely up and is constantly lit when completely down

This action applies to:

1608. Go to position, only in mode 3

Description:

Same as action 0115. Go to position, but this action will only be executed if the subject module is set to mode 3.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Position
    • 0% (compl. up) to 100% (compl. down)
    • Default value: 50%

Feedback behaviour:

LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position

This action applies to:

1609. Go to position when initiator opens, only in mode 3

Description:

Same as action 0116. Go to position when initiator opens, but this action will only be executed if the subject module is set to mode 3.

For more information about modes, see 1303. Select mode 1.

Parameters:

  • On delay
    • 0s (none)
    • 1s to 3 days
    • Continuous
    • Default value: 0s (none)
  • Position
    • 0% (compl. up) to 100% (compl. down)
    • Default value: 50%

Feedback behaviour:

LED blinks during the on delay and while the blind moves, is on when the blind reaches the set position

This action applies to: